SECTION 903 AUTOMATIC SPRINKLER SYSTEMS
* * *
[F] 903.2 Where required.
[F] 903.2.11 Specific building areas and hazards.
* * *
[Add Section B-903.2.11.7 as follows:]
B-903.2.11.7 Buildings 45 feet or more in height. An automatic sprinkler system shall be installed in the following areas of buildings that have one or more stories located 45 feet (13 716 mm) or more above the lowest level of fire department vehicle access:
1. Basements.
2. The level of exit discharge.
Exceptions:
1. Open parking structures.
2. Occupancies in Group F-2.
3. Buildings where all exterior walls have a fire separation distance of 5 feet (1524 mm) or greater.
* * *
[F] 903.3 Installation requirements.
* * *
[F] 903.3.1 Standards.
* * *
[Pursuant to the UCC, delete Section 903.3.1.2 and replace with the following:]
[F] B-903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R occupancies shall be permitted to be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions:
1. Four stories or fewer above grade plane.
2. For other than R-2 occupancies, the floor level of the highest story is 30 feet (9144 mm) or less above the lowest level of fire department vehicle access. For R-2 occupancies, the roof assembly is less than 45 feet (13716 mm) above the lowest level of fire department vehicle access. The height of the roof assembly shall be determined by measuring the distance from the lowest required fire vehicle access road surface adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest parapet, whichever yields the greatest distance.
3. The floor level of the lowest story is 30 feet (9144 mm) or less below the lowest level of fire department vehicle access
The number of stories of Group R occupancies constructed in accordance with Sections 510.2 and 510.4 shall be measured from grade plane.
* * *