SECTION 1106 MACHINERY ROOMS, GENERAL REQUIREMENTS
* * *
[Delete Section 1106.3 and replace as follows:]
M-1106.3 Class 2 and Class 3 refrigerants. Where refrigerants of Groups A2, A3 and B3 are used, the machinery room shall conform to the Class 1. Division 2, hazardous location classification requirements of NFPA 70.
* * *
[Delete Section 1106.4 in its entirety, including Table 1106.4.2, and replace as follows:]
M-1106.4 Group A2L and B2L Refrigerant. Machinery rooms for Group A2L and B2L refrigerant shall comply with Sections 1106.4. through Section 1106.4.3.
M-1106.4.1 Elevated Temperatures. Open flame-producing devices or continuously operating hot surfaces over 1290°F (700°C) shall not be permanently installed in the room.
M-1106.4.2 Refrigerant detector. In addition to the requirements of Section 1105.3, refrigerant detectors shall signal an alarm and activate the ventilation system in accordance with the response time specified in Table 1106.4.2.
Table M-1106.4.2
Group A2L and B2l Detector Activation
Activation Level | Maximum Response Time (seconds) | ASHRAE 15 Ventilation Level | Alarm Reset | Alarm Type
Less than or equal to the OEL in Table 1103.1 | 300 | 1 | Automatic | Trouble
Less than or equal to the refrigerant concentration level in Table 1103.1 | 15 | 2 | Manual | Emergency
M-1106.4.3 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system complying with ASHRAE 15.
* * *
Cite as: Phila. Code Title 4, § M-1106 — https://phillycitylaw.pages.dev/title-4/M-1106