SECTION 1109 REFRIGERANT PIPE INSTALLATION


SECTION 1109 REFRIGERANT PIPE INSTALLATION

* * *

[Delete Section 1109.2.2 and replace as follows:]

M-1109.2.2 Refrigerant and pipe enclosure. Refrigerant piping shall be protected by locating it within the building elements or within protective enclosures.

Exception: Piping protection within the building elements or protective enclosure shall not be required in any of the following locations:

1. Where installed without ready access or located more than 7 feet 3 inches (2210 mm) above the finished floor.

2. Where located within 6 feet (1829 mm) of the refrigerant unit or appliance.

3. Where located in a machinery room complying with Section 1105.

4. Outside the building:

4.1. Protected from damage from the weather, including but not limited to, hail, ice, and snow loads and

4.2. Protected from damage within the expected foot or traffic path or

4.3 Outside, underground, installed not less than 8 inches (200 mm) below finished grade and protected against corrosion.

[Delete Section 1109.2.3 and replace as follows:]

M-1109.2.3 Prohibited Locations. Refrigerant piping shall not be installed in any of the following locations:

1. Exposed within a fire resistance-rated exit access corridor.

2. Exposed within an interior exit stairway.

3. Within an interior exit ramp.

4. Within an exit passageway.

5. Within an elevator, dumbwaiter or other shaft containing a moving object.

* * *

[Delete Section 1109.2.5 and replace as follows:]

M-1109.2.5 Refrigerant pipe shafts. Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in a fire-resistance-rated shaft enclosure. The fire-resistance-rated shaft enclosure shall comply with Section 713 of the International Building Code.

Exceptions:

1. Refrigeration systems using R-718 refrigerant (water).

2. Piping in a direct refrigeration system where the refrigerant quantity does not exceed the limits of Table 1103.1 for the smallest occupied space through which the piping passes.

3. Piping located on the exterior of the building where vented to the outdoors.

* * *

[Delete Section 1109.2.6 and replace as follows:]

M-1109.2.6 Exposed piping surface temperature. Exposed piping with ready access to nonauthorized personnel having surface temperatures greater than 120°F (69°C) or less than 5°F (-15°C) shall be protected from contact or shall have thermal insulation that limits the exposed insulation surface temperature to a range of 5°F (-15°C) to 120°F (69°C).

* * *

[Delete Section 1109.2.7 and replace as follows:]

M-1109.2.7 Pipe identification. Refrigeration pipe located in areas other than the room or space where the refrigerating equipment is located shall be identified. The pipe identification shall be located at intervals not exceeding 20 feet (6096 mm) on the refrigerant piping or pipe insulation. The minimum height of lettering of the identification label shall be 1/2 inch (12.7 mm). The identification shall indicate the refrigerant designation and safety group classification of refrigerant used in the piping system. For Group A2L and B2L refrigerants, the identification shall also include the following statement: “WARNING - Risk of Fire. Flammable Refrigerant.” For Group A2, A3, B2 and B3 refrigerants, the identification shall also include the following statement: “DANGER - Risk of Fire or Explosion. Flammable Refrigerant.” For any Group B refrigerant, the identification shall also include the following statement: “DANGER - Toxic Refrigerant.”

* * *

[Delete Section 1109.3 and replace as follows, but leave Table 10.9.3.2 unchanged:]

M-1109.3 Installation requirements for Group A2L, A2, A3, B2L, B2, or B3 refrigerant. Piping systems using Group A2L, A2, A3, B2L, B2, or B3 refrigerant shall comply with the requirements of Section 1109.3.1 and 1109.3.2.

M-1109.3.1 Pipe Protection. In addition to the requirements of Section 305.5, aluminum, copper, and steel tube used for Group A2, A3, B2L, B2, and B3 refrigerants and located in concealed locations where tubing is installed in studs, joists, rafters or similar member spaces, and located less than 1-1/2 inches (38 mm) from the nearest edge of the member, shall be continuously protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch (1.46 mm) (No. 16 gage) shall cover the area of the tube plus the areas extending not less than 2 inches (51 mm) beyond both sides of the tube.

M-1109.3.2 Shaft ventilation. Refrigerant pipe shafts with systems using Group A2L or B2L refrigerant shall be naturally or mechanically ventilated. Refrigerant pipe shafts with one or more systems using any Group A2, A3, B2, or B3 refrigerant shall be continuously mechanically ventilated and shall include a refrigerant detector. The shaft ventilation exhaust outlet shall comply with Section 501.3.1. Naturally ventilated shafts shall have a pipe, duct or conduit not less than 4 inches (102 mm) in diameter that connects to the lowest point of the shaft and extends to the outdoors. The pipe, duct or conduit shall be level or pitched downward to the outdoors. Mechanically ventilated shafts shall have a minimum airflow velocity in accordance with Table 1109.3.2. The mechanical ventilation shall be continuously operated or activated by a refrigerator. Systems utilizing a refrigerant detector shall activate the mechanical ventilation at a maximum refrigerant concentration of 25 percent of the lower flammable limit of the refrigerant. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The shaft shall not be required to be ventilated for double-wall refrigerant pipe where the interstitial space of the double-wall pipe is vented to the outdoors.

* * *

[Delete Section 1109.4 in its entirety, without substitution]

* * *

[Delete Section 1109.7 in its entirety, without substitution]

* * *