SECTION 710 DRAINAGE SYSTEM SIZING


SECTION 710 DRAINAGE SYSTEM SIZING

P-710.1 Maximum fixture unit load. The maximum number of drainage fixture units connected to a given size of building sewer, building drain or horizontal branch of the building drain shall be determined using Table P-710.1(1). The maximum number of drainage fixture units connected to a given size of horizontal branch or vertical soil or waste stack shall be determined using Table 710.1(2).

TABLE P-710.1(1)
BUILDING DRAINS AND SEWERS

Diameter of Pipe (inches) | Maximum Number of Drainage Fixture Units Connected to Any Portion of the Building Drain or the Building Sewer, Including Branches of the Building Drain
Slope per Foot
1/16-inch | 1/8-inch | 1/4-inch | 1/2-inch
* * *
3 | - | 36 - | 42 | 50
* * *

* * *