R402 BUILDING THERMAL ENVELOPE
* * *
[Pursuant to the UCC, delete Table R402.1.2 and replace as follows:]
TABLE EC-R402.1.2 (N1102.1.2)
MAXIMUM ASSEMBLY U-FACTORS a AND FENESTRATION REQUIREMENTS
CLIMATE ZONE | FENESTRA- TION U-FACTOR b | SKYLIGHT U-FACTOR | GLAZED FENESTRA- TION SHGC d, e | CEILING U-FACTOR | FRAME WALL U-FACTOR | MASS WALL U-FACTOR b | FLOOR U-FACTOR | BASEMENT WALL U-FACTOR | CRAWL SPACE WALL U-FACTOR
CLIMATE ZONE | FENESTRA- TION U-FACTOR b | SKYLIGHT U-FACTOR | GLAZED FENESTRA- TION SHGC d, e | CEILING U-FACTOR | FRAME WALL U-FACTOR | MASS WALL U-FACTOR b | FLOOR U-FACTOR | BASEMENT WALL U-FACTOR | CRAWL SPACE WALL U-FACTOR
1 | 0.50 | 0.75 | 0.25 | 0.035 | 0.084 | 0.197 | 0.064 | 0.360 | 0.477
2 | 0.40 | 0.65 | 0.25 | 0.030 | 0.084 | 0.165 | 0.064 | 0.360 | 0.477
3 | 0.32 | 0.55 | 0.25 | 0.030 | 0.060 | 0.098 | 0.047 | 0.091 | 0.136
4 except Marine | 0.32 | 0.55 | 0.40 | 0.026 | 0.060 | 0.098 | 0.047 | 0.059 | 0.065
5 and Marine 4 | 0.30 | 0.55 | NR | 0.026 | 0.051 | 0.082 | 0.033 | 0.050 | 0.055
6 | 0.30 | 0.55 | NR | 0.026 | 0.045 | 0.060 | 0.033 | 0.050 | 0.055
7 and 8 | 0.30 | 0.55 | NR | 0.026 | 0.045 | 0.057 | 0.028 | 0.050 | 0.055
| | | | | | | | |
a. Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source.
b. Mass walls shall be in accordance with Section R402.2.5. Where more than half the insulation is on the interior, the mass wall U-factors shall not exceed 0.17 in Climate Zone 1, 0.14 in Climate Zone 2, 0.12 in Climate Zone 3, 0.087 in Climate Zone 4 except Marine, 0.065 in Climate Zone 5 and Marine 4, and 0.057 in Climate Zones 6 through 8.
c. In warm-humid locations as defined by Figure R301.1 and Table R301.1, the basement wall U-factor shall not exceed 0.360.
d. The SHGC column applies to all glazed fenestration.
Exception: In Climate Zones 0 through 3, skylights shall be permitted to be excluded from glazed fenestration SHGC requirements provided that the SHGC for such skylights does not exceed 0.30.
e. There are no SHGC requirements in the Marine Zone.
f. A maximum U-factor of 0.32 shall apply in Marine Climate Zone 4 and Climate Zones 5 through 8 to vertical fenestration products installed in buildings located either:
1. Above 4,000 feet in elevation above sea level, or
2. In windborne debris regions where protection of openings is required by Section R301.2.1.2. of the International Residential Code.
* * *
[Pursuant to the UCC, delete Table R402.1.3 and replace as follows:]
TABLE R402.1.3 (N1102.1.3)
INSULATION MINIMUM R-VALUE AND FENESTRATION REQUIREMENTS BY COMPONENT a
CLIMATE ZONE | FENESTRA- TION U-FACTOR b | SKYLIGHT b U-FACTOR | GLAZED FENESTRA- TION SHGC b, e | CEILING R-FACTOR | WOOD FRAME WALL R-VALUE | MASS WALL R-VALUE i | FLOOR R-VALUE | BASEMENT c WALL R-VALUE | SLAB d R-VALUE & DEPTH | CRAWL SPACE c WALL R-VALUE
CLIMATE ZONE | FENESTRA- TION U-FACTOR b | SKYLIGHT b U-FACTOR | GLAZED FENESTRA- TION SHGC b, e | CEILING R-FACTOR | WOOD FRAME WALL R-VALUE | MASS WALL R-VALUE i | FLOOR R-VALUE | BASEMENT c WALL R-VALUE | SLAB d R-VALUE & DEPTH | CRAWL SPACE c WALL R-VALUE
1 | NR | 0.75 | 0.25 | 30 | 13 | 3/4 | 13 | 0 | 0 | 0
2 | 0.40 | 0.65 | 0.25 | 38 | 13 | 4/6 | 13 | 0 | 0 | 0
3 | 0.32 | 0.55 | 0.25 | 38 | 20 or 13 + 5 h | 8/13 | 19 | 5/13 f | 0 | 5/13
4 except Marine | 0.32 | 0.55 | 0.40 | 49 | 20 or 13 + 5 h | 8/13 | 19 | 10/13 | 10, 2 ft | 10/13
5 and Marine 4 | 0.30 | 0.55 | NR | 49 | 23 or 13 + 7.5 h or 20 + 3.8 h | 13/17 | 30 g | 15/19 | 10, 4 ft or 15, 3 ft | 15/19
6 | 0.30 | 0.55 | NR | 49 | 20 + 5 h or 13 + 10 h | 15/20 | 30 g | 15/19 | 10, 4 ft | 15/19
7 and 8 | 0.30 | 0.55 | NR | 49 | 20 + 5 h or 13 + 10 h | 19/21 | 38 g | 15/19 | 10, 4 ft | 15/19
| | | | | | | | | |
For SI: 1 foot = 304.8 mm. NR = Not Required.
a. R-values are minimums. U-factors and SHGC are maximums. Where insulation is installed in a cavity that is less than the label or design thickness of the insulation, the installed R-value of the insulation shall be not less than the R-value specified in the table.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
Exception: In Climate Zones 1 through 3, skylights shall be permitted to be excluded from glazed fenestration SHGC requirements provided that the SHGC for such skylights does not exceed 0.30.
c. the interior of the basement wall. “15/19” means R-15 continuous insulation on the interior or exterior of the home or R-19 cavity insulation on the interior of the basement wall. Alternatively, compliance with “15/19” shall be R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the home.
d. R-5 insulation shall be provided under the full slab area of a heated slab in addition to the required slab edge insulation R-value for slabs. as indicated in the table. The slab edge insulation for heated slabs shall not be required to extend below the slab.
e. There are no SHGC requirements in the Marine Zone.
f. Basement wall insulation shall not be required in warm-humid locations as defined by Figure R301.1 and Table R301.1.
g. Alternatively, insulation sufficient to fill the framing cavity providing not less than an R-value of R-19.
h. The first value is cavity insulation, the second value is continuous insulation. Therefore, as an example, “13+5” means R-13 cavity insulation plus R-5 continuous insulation.
i. Mass walls shall be in accordance with Section R402.2.5. The second R-value applies where more than half of the insulation is on the interior of the mass wall.
* * *