R403 SYSTEMS
* * *
[Pursuant to the UCC, delete Section R403.3.7and replace as follows:]
EC-R403.3.7 (N1103.3.7) Building cavities (Mandatory). Building framing cavities shall not be used as supply ducts.
* * *
[Pursuant to the UCC, delete Section R403.5.1.1 and replace as follows:]
EC-R403.5.1.1 (N1103.5.1.1) Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosyphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. The controls shall limit the temperature of the water entering the cold water piping to no greater than 104ºF (40ºC).
Exception: Where the entire hot water piping system (both supply and return) are insulated with a minimum R3 insulation, the stated controls are not required.
EC-R403.5.1.1.1 Demand recirculation water systems. Where installed, demand recirculation water systems shall have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture or sensing the flow of hot or tempered water to a fixture fitting or appliance.
EC-R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy.
* * *