R405 TOTAL BUILDING PERFORMANCE


R405 TOTAL BUILDING PERFORMANCE

* * *

[Pursuant to the UCC, delete Section R405.3.2 and replace as follows:]

EC-R405.3.2 (N1105.3.2) Compliance report. Compliance software tools shall generate a report that documents that the proposed design complies with Section R405.4 (N1105.4). A compliance report on the proposed design shall be submitted with the application for the building permit. Upon completion of the building, a compliance report based on the as-built condition of the building shall be submitted to the code official before a certificate of occupancy is issued. Batch sampling of buildings to determine energy code compliance for all buildings in the batch shall be prohibited.

Compliance reports shall include information in accordance with Sections R405.43.2.1 (N1105.43.2.1 ) and R405.43.2.2 (N1105.43.2.2). Where the proposed design of a building could be built on different sites where the cardinal orientation of the building on each site is different, compliance of the proposed design for the purposes of the application for the building permit shall be based on the worst- case orientation, worst-case configuration, worst-case building air leakage and worst-case duct leakage. Such worst-case parameters shall be used as inputs to the compliance software for energy analysis.

EC-R405.3.2.1 (N1105.3.2.1) Compliance report for permit application. A compliance report submitted with the application for building permit shall include the following:

1. Building street address, or other building site identification.

2. A statement indicating that the proposed design complies with Section R405.2 (N1105.2).

3. An inspection checklist documenting the building component characteristics of the proposed design as indicated in Table R405.4.2(1) (N1105.4.2(1)). The inspection checklist shall show results for both the standard reference design and the proposed design with user inputs to the compliance software to generate the results.

4. A site-specific energy analysis report that is in compliance with Section R405.2 (N1105.2).

5. The name of the individual performing the analysis and generating the report.

6. The name and version of the compliance software tool.

EC-R405.3.2.2 (N1105.3.2.2) Compliance report for certificate of occupancy. A compliance report submitted in order to obtain the certificate of occupancy shall include the following:

1. Building street address, or other building site identification.

2. Declaration of the total building performance path on the title page of the energy report.

3. A statement bearing the name of the individual performing the analysis and generating the report, indicating that the as-built building complies with Section R405.2 (N1105.2).

4. The name and version of the compliance software tool.

5. A site-specific energy analysis report that is in compliance with Section R405.2 (N1105.2).

6. A final confirmed certificate indicating compliance based on inspection, and a statement indicating that the confirmed rated design of the built home complies with Section R405.2 (N1105.2). The certificate shall report the energy features that were confirmed to be in the home, including component-level insulation R-values or U-factors; results from any required duct system and building envelope air leakage testing; and the type and rated efficiencies of the heating, cooling, mechanical ventilation and service water heating equipment installed.

7. Where on-site renewable energy systems have been installed, the certificate shall report the type and production size of the installed system.

* * *

[Pursuant to the UCC, delete Table R405.4.2 (1) (N1105.4.2(1)) and replace as follows:]

TABLE EC- R405.4.2(1) (N1105.4.2(1)) SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS
BUILDING COMPONENT | STANDARD REFERENCE DESIGN | PROPOSED DESIGN
TABLE EC- R405.4.2(1) (N1105.4.2(1)) SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS
BUILDING COMPONENT | STANDARD REFERENCE DESIGN | PROPOSED DESIGN
Above-grade walls | Type: mass where the proposed wall is a mass wall otherwise wood frame. | As proposed
Gross area: same as proposed. | As proposed
U-factor: as specified in Table R402.1.2. | As proposed
Solar absorptance = 0.75 | As proposed
Emittance = 0.90 | As proposed
Basement and crawl space walls | Type: same as proposed. | As proposed
Gross area: same as proposed. | As proposed
U-factor: as specified in Table R402.1.2, with the insulation layer on the interior side of walls. | As proposed
Above-grade floors | Type: Wood frame. | As proposed
Gross area: same as proposed. | As proposed
U-factor: as specified in Table R402.1.2. | As proposed
Ceilings | Type: wood frame. | As proposed
Gross area: same as proposed. | As proposed
U-factor: as specified in Table R402.1.2. | As proposed
Roofs | Type: compositions shingle on wood sheathing. | As proposed
Gross area: same as proposed. | As proposed
Solar absorptance = 0.75 | As proposed
Emittance = 0.90 | As proposed
Attics | Type: vented with an aperture of 1 ft2 per 300 ft2 of ceiling area. | As proposed
Foundations | Type: same as proposed. | As proposed
Foundation wall area above and below grade and soil characteristics: same as proposed. | As proposed
Opaque doors | A = 40 ft2 | As proposed
Orientation: North. | As proposed
U-factor: same as fenestration as specified in Table R402.1.2. | As proposed
Vertical fenestration other than opaque doors | Total area h = a. The proposed glazing area, where the proposed glazing area is less than 15 percent of the conditioned floor area. b. 15 percent of the conditioned floor area, where the proposed glazing area is 15 percent or more of the conditioned floor area. | As proposed
Orientation: equally distributed to four cardinal compass orientations (N, E, S & W). | As proposed
U-factor: as specified in Table R402.1.2. | As proposed
SHGC: as specified in Table N1102.1.2 except for climate zones without an SHGC requirement, the SHGC shall be equal to 0.40 . | As proposed
Interior shade fraction: 0.9 - (0.21 × SHGC for the standard reference design). | Interior shade fraction 0.92 - (0.21 × SHGC as proposed).
External shading: none. | As proposed
Skylights | None. | As proposed
Thermally isolated sunrooms | None. | As proposed
Air exchange rate | The air leakage rate at a pressure of 0.2 inch w.g. (50 Pa) shall be Climate Zones 1 and 2: 5 air change per hour. Climate Zones 3 through 8: 3 air changes per hour. The mechanical ventilation rate shall be in addition to the air leakage rate and shall be the same as in the proposed design, but greater than 0.01 x CFA + 7.5 × (Nbr + 1). Where: CFA = conditioned floor area, ft2 Nbr = number of bedrooms Energy recovery shall not be assumed for mechanical ventilation. | The measured air exchange rate b. The mechanical ventilation rate b shall be in addition to the air leakage rate and shall be as proposed.
Mechanical ventilation | Where mechanical ventilation is not specified in the proposed design: None. Where mechanical ventilation is specified in the proposed design, the annual vent fan energy use, in units of kWh/yr, shall equal (l/ef) × [0.0876 × CFA + 65.7 × (Nbr + 1)]. Where: ef = the minimum exhaust fan efficacy, a specified in Table R403.6.1, corresponding to a flow rate of 0.01 × CFA + 7.5 × (Nbr + 1) CFA = conditioned floor area, ft2 Nbr = number of bedrooms | As proposed
Internal gains | Gain, in units of BTU/day per dwelling unit, shall equal 17.900 + 23.8 × CFA + 4,104 × Nbr Where: CFA = conditioned floor area, ft2 Nbr = number of bedrooms | Same as standard reference design
Internal mass | Internal mass for furniture and contents: 8 pounds per square feet of floor area. | Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementc but not integral to the building envelope or structure.
Structural mass | For masonry floor slabs: 80 percent of floor area covered by R-2 carpet and pad, and 20 percent of floor directly exposed to room area. | As proposed
For masonry basement walls, as proposed, but with insulation as specified in Table R402.1.3 located on the interior side of the walls. | As proposed
For other walls, ceilings, floors, and interior walls: wood frame construction. | As proposed
Heating systems d, e | For other than electric heating without a heat pump: as proposed. Where the proposed design utilizes electric heating without a heat pump, the standard reference design shall be an air source heat pump meeting the requirements of Section C403 of the IECC - Commercial Provisions. Capacity: sized in accordance with Section N1103.7. | As proposed
Cooling systems d, f | As proposed. Capacity: sized in accordance: with Section N1103.7. | As proposed
Service water heating d, e, f, g | As proposed. Use: same as proposed design. | As proposed Use, in units of gal/day = 30 + (10 × Nbr) Where: Nbr = number of bedrooms
Thermal distribution systems | Duct insulation: in accordance with Section N1103.3.1. A thermal distribution system efficiency (DSE) of 0.88 shall be applied to both the heating and cooling system efficiencies for all systems other than tested duct systems. Exception: For non-ducted heating and cooling systems that do not have a fan, the standard reference design thermal distribution system efficiency (DSE) shall be 1. For tested duct systems, the leakage rate shall be 4 cfm per 100 sf of conditioned floor area at a pressure differential of 0.1-inch w.g. (25 Pa). | Duct insulation: as proposed. As tested or, where not tested, as specified in Table R405.4.2(2).
Thermostat | Type: Manual, cooling temperature setpoint = 75 degrees F Heating temperature setpoint = 72 degrees F | Same as standard reference design.
| |

For SI: 1 square foot = 0.93 m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (US) = 3.785 L, °C = (°F - 32)/1.8, 1 degree = 0.79 rad.

a. Where required by the code official, testing shall be conducted by an approved party. Hourly calculations as specified in the ASHRAE Handbook of Fundamentals, or the equivalent, shall be used to determine the energy loads resulting from infiltration.

b. The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with Equation 43 of 2001 ASHRAE Handbook of Fundamentals, page 26.24 and the “Whole-house Ventilation” provisions of 2001 ASHRAE Handbook of Fundamentals, page 26.19 for intermittent mechanical ventilation.

c. Thermal storage element shall mean a component that is not part of the floors, walls or ceilings that is part of a passive solar system, and that provides thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element shall be in the same room as fenestration that faces within 15 degrees (0.26 rad) of true south, or shall be connected to such a room with pipes or ducts that allow the element to be actively charged.

d. For a proposed design with multiple heating, cooling or water heating systems using different fuel types, the applicable standard reference design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for each equipment and fuel type present.

e. For a proposed design without a proposed heating system, a heating system having the prevailing federal minimum efficiency shall be assumed for both the standard reference design and proposed design.

f. For a proposed design home without a proposed cooling system, an electric air conditioner having the prevailing federal minimum efficiency shall be assumed for both the standard reference design and the proposed design.

g. For a proposed design with a nonstorage-type water heater, a 40-gallon storage-type water heater having the prevailing federal minimum energy factor for the same fuel as the predominant heating fuel type shall be assumed. For a proposed design without a proposed water heater, a 40-gallon storage-type water heater having the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed for both the proposed design and standard reference design.

h. For residences with conditioned basements, R-2 and R-4 residences, and for townhouses, the following formula shall be used to determine glazing area:

AF = As * FA * F

Where:

AF = Total glazing area.

As = Standard reference design total glazing area.

FA = (Above-grade thermal boundary gross wall area)/(above-grade boundary wall area + 0.5 × below-grade boundary wall area).

F = (Above-grade thermal boundary wall area)/(above-grade thermal boundary wall area + common wall area) or 0.56, whichever is greater.

And where:

Thermal boundary wall is any wall that separates conditioned space from unconditioned space or ambient conditions.

Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.

Below-grade boundary wall is any thermal boundary wall in soil contact.

Common wall area is the area of walls shared with an adjoining dwelling unit. L and CFA are in the same units.

* * *